- compact multichannel controller with data logging capabilities
- analog / digital /universal inputs
- thermocouple / RTD inputs
- counter / flowmeter/ ratemeter inputs
- current or relay / SSR outputs
- USB Host port for flush data storage
- free configuration and recording software
- 3.5"/5.7 TFT, 320 x 240 pixels, touchscreen navigation
The device can simultaneously record all build-in logical channels, and is capable to record data with maximum speed 10Hz (ten samples per second, with some limitation of number of recorded channels). 1.5GB of internal data memory is enough for continuous recording of all channels with a speed of 1 sample per second (each channel) for over 50 days (250 000 000 samples in total!). An operator can download stored data using a USB flashdisk or via Ethernet.
Datalogger - Controller Models
Models |
PMS 110 R |
PMS 111 R |
Display
|
3.5" graphic TFT, 320 x 240 pixels, touchscreen navigation |
5.7" graphic TFT, 320 x 240 pixels, touchscreen navigation |
Input |
- 48 analogue inputs (0/4-20 mA, 0/1-5V or 0/2-10V) max.
- 48 digital inputs max.
- 24 Thermocouple inputs max. (J,K, S, T, N, R, B, E)- 12 RTD inputs max.
- 9 universal inputs (U/I/RTD/TC/mV) max
- 12 counter inputs max
- 12 flowmeter/ratemeter inputs
- Digital input: 1 x 24V DC, optocoupled
|
- 72 analogue inputs (0/4-20 mA, 0/1-5V or 0/2-10V) max
- 72 digital inputs max
- 36 Thermocouple inputs max.(J,K, S, T, N, R, B, E), 18 RTD inputs max
- 15 universal inputs (U/I/RTD/TC/mV) max
- 12 counter inputs max
- 12 flowmeter/ratemeter inputs
- Digital input: 1 x 24V DC, optocoupled
|
Output |
- 8 analog (4-20 mA
- 16 relay (1A/250V) / SSR outputs or 4 relay 5A/250V max.
- Remote inputs and outputs available, via RS-485/Modbus RTU
|
- 18 analog (4-20 mA) max
- 36 relay (1A/250V), 72 SSR outputs or 18 relay 5A/250V max.
- Remote inputs and outputs available, via RS-485/Modbus RTU
|